Implemented CANopen Objects
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
CAN-CBX-THERMO
Page 64 of 123
8.9.10 Guard Time (100C
h
) und Life Time Factor (100D
h
)
The CAN-CBX module supports the node guarding or alternatively the heartbeat function (see page 74).
NOTICE
By the recommendation of the CiA, the heartbeat-function shall be used preferentially.
Use the node-guarding only for existing systems and not for new developments!
Guard time and life time factors are evaluated together. Multiplying both values will give you the life
time. The guard time is represented in milliseconds.
INDEX
100C
h
Name
guard time
Data type
unsigned 16
Access mode
rw
Default value
0 [ms]
Minimum value
0
Maximum value
FFFF
h
(65.535 s)
INDEX
100D
h
Name
life time factor
Data type
unsigned 8
Access mode
rw
Default value
0
Minimum value
0
Maximum value
FF
h