Manufacturer Specific Profile Area
CAN-CBX-THERMO
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
Page 105 of 123
SR_x
SR_x
Floating
Average
VAL
OUT
Average
8.11.5 Average N (2403
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
2403
0
Number_of_entries
4
4
unsigned 8
ro
1
average_count_1
0...4
0
unsigned 8
rw
2
average_count_2
0...4
0
unsigned 8
rw
3
average_count_3
0...4
0
unsigned 8
rw
4
average_count_4
0...4
0
unsigned 8
rw
Description of the parameter average_count_x (x = 1...4):
This parameter defines how many analog values are used to calculate the moving average.
After every conversion a new average is available, because the A/D-values are buffered in a ring buffer.
The number of averaged values is:
m ... Number of averaged values
m = 2
(average_count_x)
Thus it can be averaged over the last 1, 2, 4, 8 or 16 values.
Features:
• Filter with decimation
• Improvement of the resolution
• A new average is available after every conversion
• Step response is 2
m
¹
T
Data
(see object 2402
h
)
INFORMATION
The input for “Average” (object 2403
h
) is “Val
OUT
” configured by object 2402
h
!
Description of the Filter:
SR_x ...
sample rate