Device Profile Area
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
CAN-CBX-THERMO
Page 92 of 123
8.10.8 AI Decimal Digits PV (6132
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
6132
h
0
Number_of_entries
4
4
unsigned 8
ro
1
AI_decimal_digits_PV_1
0...3
3
unsigned 8
rw
2
AI_decimal_digits_PV_2
0...3
3
unsigned 8
rw
3
AI_decimal_digits_PV_3
0...3
3
unsigned 8
rw
4
AI_decimal_digits_PV_4
0...3
3
unsigned 8
rw
Description of the parameter AI_decimal_digits_PV_x (x = 1...4):
This parameter contains the number of fractional digits of the process value (PV) in object “AI_PV”
(9130
h
).
The value of the parameter gives the number of the decimal digits.
Example:
AI_decimal_digits_PV_1 = 3
Value in object AI_PV_1 = 123456
d
Measured value: 123.456
µ
V (at default setting (voltage measurement) see object 6110
h
).