Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40
54
00-02-0939
2019-06-13
40241
Read Only
Modbus EEPROM Values Saved Confirmation
(Saved = 1)
(0 or 1)
40242
Read Only
Active Warning Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Low Fuel Warn
(0 or 1)
1 = Fuel Leak Warn
(0 or 1)
2 = Fuel Filter Restriction Warn
(0 or 1)
3 = Low Lube Level Warn
(0 or 1)
4 = Coolant Level Warn
(0 or 1)
5 = Water in Fuel Warn
(0 or 1)
6 = No Flow Warn
(0 or 1)
7 = High Engine Oil Temp Warn
(0 or 1)
8 = Low Oil Pressure Warn
(0 or 1)
9 = High Engine Temp Warn
(0 or 1)
10 = High Discharge Pressure Warn
(0 or 1)
11 = Low Discharge Pressure Warn
(0 or 1)
12 = High Suction Warn
(0 or 1)
13 = Low Suction Warn
(0 or 1)
14 = High Level Warn
(0 or 1)
15 = Low Level Warn
(0 or 1)
40243
Read Only
Active Warning Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = High Flow Warn
(0 or 1)
1 = Low Flow Warn
(0 or 1)
2 = Reserved
(0 or 1)
3 = Reserved
(0 or 1)
4 = Low Gear Box Pressure Warn
(0 or 1)
5 = High Gear Box Pressure Warn
(0 or 1)
6 = Reserved
(0 or 1)
7 = Reserved
(0 or 1)
8 = Reserved
(0 or 1)
9 = Low Engine Temp Warn
(0 or 1)
10 = Reserved
(0 or 1)
11 = Reserved
(0 or 1)
12 = Run To Destruct Warn
(0 or 1)
13 = Battery High Warn
(0 or 1)
14 = Battery Low Warn
(0 or 1)
15 = Amber Lamp Status
(0 or 1)
40244
Read Only
Active Warning Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Pivot Alignment Warn
(0 or 1)
1 = Reserved
Reserved
2 = Reserved
Reserved
3 = Reserved
Reserved
4 = Reserved
Reserved
5 = Reserved
Reserved
6 = Reserved
Reserved
7 = Reserved
Reserved
8 = Reserved
Reserved
9 = Reserved
Reserved
10 = Reserved
Reserved