Section 40
20
00-02-0939
2019-06-13
Setting
up to Auto Start on Level
1. Access
Menu/Application Configuration.
Press the down arrow to
Auto Start/Stop Function
then
press
[Enter]
.
2. Utilize the Up and Down arrows to select
Level Transducer
then press
[Enter].
3. Utilize the Up and Down arrows to select
Level Transducer
in the main application configuration
menu.
4. Complete the parameters that apply. (Start/Stop Level and Level Maintain Type, See Menu Glossary
for explanation of settings.)
5. Press
[Back]
twice and access
Input_Output/Analog Inputs.
6. Select the Analog Input to modify for the level transducer.
7. Assign 4-20mA System Level as the function for the selected Analog Input.
8. Press
[Back]
once to get back to the Analog Input menu.
9. Press the arrow up or arrow down key. Select
Sensor Setup
then press
[Enter]
.
10. Select System Level to set up then press
[Enter]
.
11. Set the offset of the 4mA if needed to calibrate the low side then press
[Enter]
.
12. Set the range of the transducer on the high side then press
[Enter].
(i.e., 0-10ft transducer would
show 4mA at 0 ft. and 20mA at 10 ft.)
13. Press
[Back]
twice to return to the main menu.
14. Utilize the Up and Down arrows to select
Advanced Engine Settings
then press
[Enter]
.
15. Utilize the Up and Down arrows to select
Warnings and Shutdowns
then press
[Enter].
16. Utilize the Up and Down arrows to set the
High and Low Level
warnings and shutdowns.
17. Press the
[Menu]
key to exit the menu setup screens.
Setting to Auto Start on Clock
NOTES:
1)
Ensure the correct date and time are established in the System menu prior to
establishing the Auto Start on Clock settings.
2)
The Clock start timer is independent of other auto start start/stop functions. When
started from the clock the controller will shut down the engine from the clock.
1. Access
Menu/Start_Stop Timers
, and select the first Start/Stop Timer.
2. Select Start Day 1 and then select the appropriate day or Daily.
3. Select Start Time 1 and establish the hour, minute and second to start.
4. Establish the Stop Day and Time as in steps 2-3.
5. Press the
[Menu]
key to exit the menu setup screens.
NOTE:
The MPC-10 / TEC-10 has the ability to establish three different Start/Stop dates
and times. If desired, repeat steps 1-3 for subsequent Timers.
Setting to Auto Start on Temperature
1.
Access
Menu/Application Configuration.
Press the down arrow to
Auto Start/Stop Function
then
press
[Enter]
.
2. Utilize the Up and Down arrows to select
Temperature Transducer
then press
[Enter].
3. Utilize the Up and Down arrows to select
Temperature Transducer
in the main application
configuration menu.
4. Establish a Start and Stop Temperature, and press
[Back]
twice.
5. Utilize the Up and Down arrows to select
Input_Output/Analog Inputs
then press
[Enter].
6. Select the Analog Input to modify for the temperature transducer.