allows for pumps of many variations to be used in a manual/auto start environment utilizing the
more common auto start and throttling functions.
Air Compressor:
The Air Compressor application houses the auto start functions and auto
throttle methods meant to be used on most engine-driven air compressor applications. The MPC-
10 / TEC-10 allows for the compressor to start/stop and/or maintain a desired pressure during
operation.
Hose Reel Irrigation:
The Hose Reel Irrigation application houses the auto start functions and
auto throttle methods meant to be used on hose reel irrigation systems. The MPC-10 / TEC-10
allows for the hose reel pump to auto start with several methods, including the Local Key Start
which may be the most used in this application. The key feature of this application is the auto
throttling method. This feature allows the controller to manage the pump’s throttle in order to
maintain a pressure in the hose during irrigation.
Frost Protection:
The Frost Protection application houses the auto start functions and auto
throttle methods meant to be used on frost protection systems. This application allows for wind
machine, sprinkler or other forms of frost protection using single contact or a temperature
transducer.
Chipper:
The MPC-10 / TEC-10 must be in the Manual mode for both Chipper Auto and Chipper
Manual (Autofeed Override). The Chipper application has settings required for the operation:
Auto Start / Stop Function
(Medium Security)
: Factory Set to Two Contact Maintained
Single Contact
(Pump All Purpose, Air Compressor, Hose Reel Irrigation, Frost Protection,
Chipper)
Local Start Key
(Pump All Purpose, Air Compressor, Hose Reel Irrigation, Chipper)
Two Contact Maintained
(Pump All Purpose)
Pressure Transducer
(Pump All Purpose & Air Compressor)
Level Transducer
(Pump All Purpose)
Temperature Transducer
(Frost Protection)
Auto Throttle Method
(Medium Security)
: Factory Set to Running Loaded
Running Loaded RPM
(Pump All Purpose, Air Compressor, Frost Protection) allows the controller
to adjust the speed of the engine to maintain a RPM setpoint in Auto mode.
Pressure Transducer
(Pump All Purpose, Air Compressor, Hose Reel Irrigation) allows the
controller to adjust the speed of the engine to maintain a pressure setpoint in Auto mode.
Level Transducer
(Pump All Purpose) allows the controller to adjust the speed of the engine to
maintain a level setpoint in Auto mode.
Running Loaded Inc/Dec
(Pump All Purpose) allows the controller to ramp the engine speed up
and down using the Inc/Dec buttons on the keypad while using the controller for auto start.
Auto Throttle Type
(High Security)
: Factory set to NON PID Auto Throttle.
NON PID Auto Throttle
: this throttle type does not use the PID adjustments found in the
Transducer setups in the Application menu and uses the ramp rates to control the engine speed.
PID Auto Throttle:
this throttle type uses the PID adjustments found in the Transducer setups
within the Application menu. This setting should only be used by a technician who understands in