Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40
31
00-02-0939
2019-06-13
controller will turn off the ECU enable output when a red lamp status is broadcast on the CANbus.
Factory
set to Controller & ECU
.
Engine Settings (Low Security)
Engine Type
(High Security)
:
allows the selection between J1939 and Mechanical. If Mechanical is
chosen, some parameters associated with J1939 will no longer appear in the menu.
Factory set to J1939.
Engine Manufacturer
(High Security)
:
allows the selection of the specific engine manufacturer (i.e.,
Caterpillar (M-T4F), Cummins (M-T4F), John Deere (M-T4F), Deutz (M-T4F), Kohler KDI, Kubota (M-T4i,
Gaseous), JCB (T4F), Volvo (T3-T4F), FPT (T4F), Isuzu (M), PSI (EControls ECU), Scania (T3-T4F),
FORD (EControls ECU), Perkins (M-T4F), Other, HATZ (M-T4F), GM (MEFI ECU), Yanmar (T4F).
Factory
set to Other.
Engine Emission
(High Security)
:
allows the selection of the emissions controls (i.e., Tier 3 or Less,
Interim Tier 4 or Tier 4 / EU Stage IIIA, IIIB, IV).
Factory set to Tier 3 or Less.
Tier 4
(Low Security)
:
(only appears if Interim Tier 4 or Tier 4 / EU Stage IIIA, IIIB, IV is chosen) allows
the automatic or inhibition of after treatment regeneration and/or the requesting of a regeneration.
Auto/Inhibit regen
(Low Security)
:
allows the operator to inhibit an after treatment regeneration
by setting to inhibit.
Factory set to Auto
Request Regen
(Low Security)
: s
ends a request to the engine ECU for regeneration.
Factory
set to No
DEF Gauge
(High Security)
: s
hows the DEF gauge when set to Yes.
Factory set to No
Percent Soot Gauge
(High Security)
:
shows the % Soot gauge when set to Yes.
Factory set to
No
Show Regen Screen
(High Security)
:
shows the regeneration screen in the main screens when
set to Yes.
Factory set to No
NOTE:
Inhibiting the Regen may cause the engine to de-rate or shut down if the soot level is
too high. Recommend leaving this setting in Auto Regen. The ECU may not allow the
Regen request if certain parameters do not meet the engine manufacturers
’ requested
levels.
Speed Source
(High Security)
:
allows the selection of the appropriate speed source of the engine (i.e.,
J1939, Alternator or Magnetic Pickup).
Factory set to J1939
Speed Calibration
– Pulse Count
(High Security)
:
allows the setting of the correct number of flywheel
teeth or engine alternator pulses for mechanical engines when speed source is set to Alternator or Magnetic
Pickup.
Factory set to 150
Speed Calibration
– RPM
(High Security): allows user to set the known RPM speed of the engine while
running to calculate backwards to a pulse count from the alternator or flywheel gear.
Warm Up Speed
(Medium Security)
:
allows the setting of the speed of the engine during the warm-up
phase. This speed setting must be at or above the minimum engine speed setting.
Factory set to 900
RPM