Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40
35
00-02-0939
2019-06-13
Underspeed Shutdown
(Medium Security)
:
a shutdown will occur when the engine speed
reaches this set point.
Factory set to 0 RPM
Overspeed Shutdown
(Medium Security)
:
a shutdown will occur when the engine speed reaches
this set point.
Factory set to 2400 RPM.
High Level Warning
(Medium Security)
:
an alarm will occur if the level reaches this set point.
Menu setting shown after analog input is set.
Factory set to 0.0 FT
High Level Shutdown
(Medium Security)
:
a shutdown will occur if the level reaches this set
point.
Menu setting shown after analog input is set.
Factory set to 0.0 FT.
Low Level Warning
(Medium Security)
:
an alarm will occur if the level reaches this set point.
Menu setting shown after analog input is set.
Factory set to 0.0 FT.
Low Level Shutdown
(Medium Security)
:
a shutdown will occur if the level reaches this set
point. Menu setting shown after analog input is set.
Factory set to 0.0 FT.
High Flow Warning
(Medium Security)
:
an alarm will occur if the flow reaches this set point.
Menu setting shown after analog input is set.
Factory set to 0 GPM.
High Flow Shutdown
(Medium Security)
:
a shutdown will occur if the flow reaches this set
point.
Menu setting shown after analog input is set.
Factory set to 0 GPM.
Low Flow Warning
(Medium Security)
:
an alarm will occur if the flow reaches this set point.
Menu setting shown after analog input is set.
Factory set to 0 GPM.
Low Flow Shutdown
(Medium Security)
:
a shutdown will occur if the flow reaches this set
point. Menu setting shown after analog input is set.
Factory set to 0 GPM
.
High Discharge Pressure Warning
(Medium Security)
:
an alarm will occur when the pressure
reaches this set point.
Factory set to 0 PSI.
High Discharge Pressure Shutdown
(Medium Security)
:
a shutdown will occur when the
pressure reaches this set point. Menu setting shown after analog input is set.
Factory set to 0
PSI.
Low Discharge Pressure Warning
(Medium Security)
:
an alarm will occur when the pressure
reaches this set point. Menu setting shown after analog input is set.
Factory set to 0 PSI
Low Discharge Pressure Shutdown
(Medium Security)
:
a shutdown will occur when the
pressure reaches this set point. Menu setting shown after analog input is set.
Factory set to 0
PSI
High Suction Pressure Warning
(Medium Security)
:
an alarm will occur when the pressure
reaches this set point. Menu setting shown after analog input is set.
Factory set to 0 PSI.
High Suction Pressure Shutdown
(Medium Security)
:
a shutdown will occur when the
pressure reaches this set point. Menu setting shown after analog input is set.
Factory set to 0
PSI.
Low Suction Pressure Warning
(Medium Security)
:
an alarm will occur when the pressure
reaches this set point. Menu setting shown after analog input is set.
Factory set to 0 PSI