Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40
38
00-02-0939
2019-06-13
Digital Input 2
(Medium Security)
: Factory set to Function: Auto Start Maintained, Active: B-,
Action: Not Used
Digital Input 3 (Medium Security)
: Factory set to Function: Auto Stop Maintained, Active: B-,
Action: Not Used
Digital Input 4 (Medium Security)
: Factory set to Function: Low Coolant Level, Active: B-,
Action: Shutdown
Digital Input 5
(Medium Security)
: Factory set to Function: Low Lube Oil Level, Active: B-,
Action: Shutdown
Function (Medium Security)
:
Disabled
Single Contact Start/Stop
Auto Start Maintained
(Auto Start Maintained must have Auto Stop Maintained Set)
Auto Stop Maintained
(Auto Stop Maintained must have Auto Start Maintained Set)
Remote Alarm Acknowledge
Low Fuel Level
Fuel Leak
Fuel Filter Restriction
Low Lube Oil Level
Low Coolant Level
Remote Stop
Remote Manual/Auto
Idle Engine
Water in Fuel
No Flow
User 1
User 2
Remote Throttle Inc
(allows increasing engine speed remotely)
Remote Throttle Dec
(allows decreasing engine speed remotely)
Kubota Parking Brake
(needed when Kubota engine and Tier 4 is selected)
Kubota Neutral Switch
(needed when Kubota engine and Tier 4 is selected)
Pivot Alignment
(allows a warning or shutdown when a pivot becomes misaligned)
Air Damper Closed
Air Filter Restriction
Battery Charger Fail
Oil Filter Restriction
Disable TSC1
(allows the operator to disable the TSC1 message to the engine when active)
Remote Throttle Active
(allows the operator to activate the remote throttle of the analog
inputs)
Active (Medium Security)
:
B-
(when input closes to ground it enables action of digital function)
B+
(when input closes to battery positive it enables action of digital function)
Open
(when input opens it enables action of digital function)
Action (Medium Security)
:
Not Used:
(chosen when using digital input for anything except a fault)
Warning:
(chosen for an immediate warning to the operator when function is active)
Shutdown:
(chosen for an immediate shutdown of engine when function is active)
Shutdown, Controlled:
(chosen to allow the controller to shutdown through the normal
sequence of operation including cooldown when function is active. User acknowledgement of
the fault is required to restart in Auto after shutdown occurs)
Relay Control:
(chosen for control of one of the relay outputs when function is active)
Shutdown, Controlled, Restart:
(chosen to allow the controller to shutdown through the
normal sequence of operation including cooldown when function is active. User