Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40
44
00-02-0939
2019-06-13
Pressure D
(High Security): This selection is present when PID Auto Throttle Type selected and allows
adjustment of the Derivative setting of the PID loop when throttling.
Factory set to 0.001
Level Transducer
(Medium Security): This selection is only present when selecting Level Transducer in the
Auto Start / Stop Function or Auto Throttle Method.
Start Level
(Medium Security): This selection is present when selecting Level Transducer as the Auto
Start / Stop Function. When the level reaches this set point, an auto start will occur.
Factory set to
0.0 ft
Stop Level
(Medium Security): This selection is present when selecting Level Transducer as the Auto
Start / Stop Function. When the level reaches this set point, an auto stop will occur.
Factory set to
0.0 ft
Maintain Level
(Medium Security): This selection is present when selecting Level Transducer as the
Auto Throttling Method. The engine will be throttled between the min. and max. RPM set points to
maintain this level.
Factory set to 0.0 ft
Deadband Level
(Medium Security): This selection is present when selecting Level Transducer as
the Auto Throttling Method. This extends above and below the maintain set point, no throttling occurs
while the level is in the deadband.
Factory set to 0.0 ft
Level Type
(Medium Security):
Factory set to Empty
Fill:
When the Auto Start/Stop is selected as Level Transducer and the Level Type is set to
(Fill)
, it
is necessary to set the flow to start on a low value (falling ↓) then stop on high value (rising ↑) in
order to work correctly. When the Auto Throttle Method is selected to Level Transducer and the
Level Type is set to
(Fill)
, the controller throttles the engine by increasing the RPM below the
deadband and decreasing the RPM above the deadband to maintain the desired level.
Empty:
When the Auto Start/Stop is selected as Level Transducer and the Level Type is set to
(Empty)
, it is necessary to set the level to start on a high value (rising ↑) then stop on low value
(falling ↓) in order to work correctly. When the Auto Throttle Method is selected to Level Transducer
and the Level Type is set to
(Empty)
, the controller throttles the engine by decreasing the RPM
below the deadband and increasing the RPM above the deadband to maintain the desired level.
Level P
(High Security): This selection is present when PID Auto Throttle Type selected and allows
adjustment of the Proportional setting of the PID loop when throttling.
Factory set to 0.020
Level I
(High Security): This selection is present when PID Auto Throttle Type selected and allows
adjustment of the Integral setting of the PID loop when throttling.
Factory set to 0.020
Level D
(High Security): This selection is present when PID Auto Throttle Type selected and allows
adjustment of the Derivative setting of the PID loop when throttling.
Factory set to 0.001
(Flow Transducer):
The controller supports this transducer for display and alarms only. No control such
as start stop or throttling is available. Auto Flow is available in the MPC-20 controller if required.
Temperature Transducer
(Medium Security): only present when selecting Temperature Transducer in the
Auto Start / Stop Function.
Start Temperature
(Medium Security)
:
When the temperature drops to this set point, an auto start will
occur.
Factory set to 32 F