Section 40
32
00-02-0939
2019-06-13
Warm Up Delay
(Low Security)
:
allows the operator to set the desired warm-up time/delay for the engine.
This is the length of time the engine will run at a lower speed for its warm-up cycle.
Factory set to 3
minutes
Minimum Engine Speed
(Medium Security)
:
allows the setting of the lowest engine speed for continual
operation. The controller will not allow the engine to throttle under the minimum engine speed when
maintaining pressure or level.
Factory set to 700 RPM
Maximum Engine Speed
(Medium Security)
:
allows the setting of the highest engine speed for continual
operation. The controller will not allow the engine to throttle above the maximum engine speed when
maintaining pressure or level.
Factory set to 2200 RPM
Cooldown Speed
(Medium Security)
:
allows the setting of the speed of the engine while it is cooling
down. This speed setting must be at or above the minimum engine speed setting.
Factory set to 900
RPM
Cooldown Delay
(Low Security)
:
allows the operator to set the desired cool-down time/delay for the
engine. This is the length of time the engine will run at a lower speed for its cool-down cycle.
Factory set
to 3 minutes
Advanced Engine Settings
(Low Security)
Address Claim
(High Security)
:
allows the operator to set the address claim of the controller when used
on the CANbus. This address is relative to the address the ECU requires the TSC1 to be broadcast from
along with any Tier 4 messaging. Consult your engine manufacturer or dealer to obtain the correct source
address the controller should be set to communicate correctly with the engine ECU.
Factory set to 3
and
changed per Engine Manufacturer setting
ECU Source Address
(High Security)
:
source address of the ECU being connected to. Normally set to
0, 1 or 2
per SAE J1939 specifications. This menu item is only shown if J1939 is selected for the Engine
Type.
Factory set to 0
ECU Hour Select
(High Security)
:
choose from ECU Hours (engine hours reported by the ECU) or Internal
(hours calculated internally by the MPC-10 / TEC-10) provided the RPM>50. This menu item is only shown
if J1939 is selected for the Engine Type.
Factory set to ECU Hours
Crank Attempts
(High Security)
:
format of 1.00 to 20.00. The number of times the engine will attempt to
start before providing an overcrank shutdown.
Factory set to 3
Crank Disconnect Speed
(Medium Security)
:
the speed at which the crank will disconnect barring other
input parameters.
Factory set to 500 RPM
Run To Destruct
(High Security)
:
this feature is used when the controller is not able to shut down the
engine, but allows faults to be shown on screen and LEDs per application requirement.
Factory set to
Disable
Timers/Delays
(Low Security)
:
establish operational settings for:
Auto Start Delay
(Medium Security)
:
the auto start condition must remain active throughout this
delay for an auto start to occur. If the auto start condition is removed during this delay, the delay
is reset to zero.
Factory set to 3 seconds