Teqwave F/I Modbus TCP
Electrical connection
Hauser
19
7
Electrical connection
The measuring device does not have an internal circuit breaker. For this reason,
assign the measuring device a switch or power-circuit breaker that allows the power
supply line to be easily disconnected from the mains.
7.1
Connecting requirements
7.1.1
Requirements for connecting cable
Connecting cable between sensor and transmitter
Only use the cable supplied.
Electrical safety
National regulations and standards apply.
The connecting cables provided by the customer must fulfill the following requirements.
Modbus Ethernet cable
Cable type
100 Base-TX
Cable category
Min. CAT5
Plug type
RJ-45 (8P8C)
Shielding
S/FTP, F/FTP, SF/FTP, S/UTP, F/UTP or SF/UTP
Cable length
Max. 30 m (98 ft)
Power supply and signal cables
Cable type
Strand or solid wire
Conductor cross-
section
0.129 to 1.31 mm
2
(16 to 26 AWG)
Temperature range
• –40 to 70 °C (–40 to 158 °F) when mounted in a fixed position
• –10 to 50 °C (14 to 122 °F) when cable can move freely
Cable length
Max. 30 m (98 ft)
Power supply cable
Standard installation cable is sufficient.
Analog output
Digital input
Relay output (alarm)
7.1.2
Terminal assignment
Terminal
Assignment
V+
V
in
24 V DC
Supply voltage
V-
+
out
0 to 10 V; 4 to 20 mA
Analog output
-
0
output
selection
Digital input
1
Signal ground