5 Operation
Proline Promag 51
62
Hauser
3
Read the primary process variable
as current in mA and four (preset
using Command 51) dynamic
process variables
Access type = read
none
24 bytes are sent as a response:
– Bytes 0–3: primary process variable current in mA
– Byte 4: HART unit code of the primary process
variable
– Bytes 5–8: Primary process variable
– Byte 9: HART unit code of the second process
variable
– Bytes 10–13: Second process variable
– Byte 14: HART unit code of the third process
variable
– Bytes 15–18: Third process variable
– Byte 19: HART unit code of the fourth process
variable
– Bytes 20–23: Fourth process variable
Factory setting:
• Primary process variable = Volume flow
• Second process variable = Totalizer 1
• Third process variable = not assigned
• Fourth process variable = not assigned
!
Note!
• You can set the assignment of device variables to
process variables using Command 51.
• Manufacturer-specific units are represented using
the HART unit code “240”.
6
Set HART shortform address
Access type = write
Byte 0: desired address (0...15)
Factory setting:
0
!
Note!
With an address >0 (multidrop mode), the current out-
put of the primary process variable is set to 4 mA.
Byte 0: active address
11
Read unique device identification
using the TAG (measuring point
designation)
Access type = read
Bytes 0–5: TAG
Device identification delivers information on the
device and the manufacturer. It cannot be changed.
The response consists of a 12 byte device ID if the
given TAG agrees with the one saved in the device:
– Byte 0: fixed value 254
– Byte 1: Manufacturer ID, 17 = E+H
– Byte 2: Device type ID, 67 = Promag 51
– Byte 3: Number of preambles
– Byte 4: Universal commands rev. no.
– Byte 5: Device-specific commands rev. no.
– Byte 6: Software revision
– Byte 7: Hardware revision
– Byte 8: Additional device information
– Bytes 9–11: Device identification
12
Read user message
Access type = read
none
Bytes 0–24: User message
!
Note!
You can write the user message using Command 17.
13
Read TAG, descriptor and date
Access type = read
none
– Bytes 0–5: TAG
– Bytes 6–17: descriptor
– Bytes 18–20: Date
!
Note!
You can write the TAG, descriptor and date using
Command 18.
Command No.
HART command / Access type
Command data
(numeric data in decimal form)
Response data
(numeric data in decimal form)
Содержание Proline Promag 51
Страница 4: ...QUICK SETUP commissioning Proline Promag 51 4 Endress Hauser...
Страница 10: ...1 Safety instructions Proline Promag 51 10 Endress Hauser...
Страница 52: ...4 Wiring Proline Promag 51 52 Endress Hauser...
Страница 80: ...7 Maintenance Proline Promag 51 80 Endress Hauser...
Страница 104: ...9 Trouble shooting Proline Promag 51 104 Endress Hauser...
Страница 122: ...11 Index Proline Promag 51 122 Endress Hauser...
Страница 124: ...www endress com worldwide BA080D 06 en 03 05 50101924 FM SGML6 0...