Operation
Micropilot S FMR533 4 to 20 mA HART
36
Hauser
5.4
Display and acknowledging error messages
Type of error
Errors that occur during commissioning or measuring are displayed immediately on the local
display. If two or more system or process errors occur, the error with the highest priority is the one
shown on the display.
The measuring system distinguishes between the following types of error:
•
A (Alarm):
Device goes into a defined state (e.g. MIN, MAX, HOLD)
Indicated by a constant symbol.
(For a description of the codes,
70)
•
W (Warning):
Device continue measuring, error message is displayed.
Indicated by a flashing symbol.
(For a description of the codes,
70)
•
E (Alarm / Warning):
Configurable (e.g. loss of echo, level within the safety distance)
Indicated by a constant/flashing symbol.
(For a description of the codes,
70)
5.4.1
Error messages
Error messages appear as four lines of plain text on the display. In addition, a unique error code is
also output. A description of the error codes,
70.
• The "
diagnostics
"
(0A)
function group can display current errors as well as the last errors that
occurred.
• If several current errors occur, use
O
or
S
to page through the error messages.
• The last occurring error can be deleted in the "
diagnostics
"
(0A)
function group
with the funktion "
clear last error
"
(0A2)
.
⇒