Function "empty calibr." (005)
This function is used to enter the distance from the flange (reference point of the measurement) to
the minimum level (= zero).
L00-FMR2xxxx-14-00-06-en-008
"
Caution!
For dish bottoms or conical outlets, the zero point should be no lower than the point at which the
radar beam hits the bottom of the tank.
Function "full calibr." (006)
This function is used to enter the distance from the minimum level to the maximum level (= span).
L00-FMR2xxxx-14-00-06-en-009
In principle, it is possible to measure up to the tip of the antenna. However, due to considerations
regarding corrosion and build-up, the end of the measuring range should not be chosen any closer
than 50 mm (2") to the tip of the antenna.
!
Note!
If
bypass
or
stilling well
was selected in the "
tank shape
"
(002)
function, the pipe diameter is
requested in the following step.
⇒