Commissioning
Micropilot S FMR533 4 to 20 mA HART
56
Hauser
Function "dip table mode" (033)
The dip table can be switched on or off using this function.
Selection:
• manual
• semi-automatic
• table on
•
table off
• clear table
• view
Manual
The "manual mode" of the dip table can be used to enter collected data after a series of data pairs
taken at different tank levels. The parameter "manual" in the "
dip table
"
(033)
function can be used
to enter data pairs, which have been recorded at different levels, into the dip table.
The measured value and the dip value can be entered.
• uncorrected measured value:
This is the measured value supplied by the device,
NOT
corrected by the dip table.
The choice of measured value, level or remaining fill height is dependent on the device setting.
• Dip value:
This is the level or distance to flange respectively, given by the hand dip.
This value should be used to correct the measured value.
!
Note!
The bigger the distance between the different levels while taking hand dips, the more accurate the
linearisation of the dip table will be.
Semi-automatic
The value pairs in the dip table can be read. You can enter the dip value only. When there are new
value pairs, the current uncorrected level or distance is accepted as the measured value.
Table on
The dip table is switched on.
Table off
The dip table is switched off.
Clear table
The complete dip table is deleted. The table is switched off. The number of free table entries is set
to the maximum value (
= 32
).
View
The value pairs in the dip table can
only
be read. You can still select this menu option, even if there
is no dip table available. In this case, the number of free table entries is at maximum value (
= 32
).
⇒