Micropilot S FMR533 4 to 20 mA HART
Technical data
Hauser
79
10.1.4
Auxiliary energy
Ripple HART
47 to 125 Hz: Uss = 200 mV (at 500
Ω
)
Max. noise HART
500 Hz to 10 kHz: Ueff = 2.2 mV (at 500
Ω
)
Electrical connection
T12 housing with separate terminal compartment
Load HART
Minimum load for HART communication: 250
Ω
Cable entry
• Cable gland: 2 x M20x1.5
• Cable entry: 2 x G½ or 2 x ½NPT
Supply voltage
Power consumption
• Max. 330 mW at 16 V
• Max. 500 mW at 24 V
• Max. 600 mW at 30 V
• Max. 700 mW at 36 V
Current consumption
Max. 21 mA (50 mA inrush current)
Power supply
• For stand alone operation recommended via two Hauer RN221N.
• Integrated in Tank Gauging system via Hauser Tank Side Monitor NRF50
(recommended operation mode).