Commissioning
Micropilot S FMR533 4 to 20 mA HART
58
Hauser
New point
You can enter a new point. Suggested values displayed for the measured value and dip value are the
current uncorrected level or remaining fill height. The new value pair can be altered without
selecting the "
edit point
" parameter. If the table is full, you can still select this parameter. In this
case, the number of free table entries stands at minimum value (
= 0
).
Edit point
The displayed value pair can be changed. Only the dip value can be changed with semi-automatic
input mode.
"
Caution!
To accept the value pair in the table, confirm it with "
store point
".
Store point
The displayed value pair is sorted in the table.
!
Note!
For sorting, the following criteria must be met:
• Measured variables may not be equal but have different dip values.
• A measured variable available in the table is recognised as equal when it is closer than 1 mm to
the sorting value.
• After successful sorting, the setting remains at "
edit point
" and the number of free table entries
is decremented.
"
Caution!
If the value cannot be sorted, the setting remains at the previous menu option.
No warning or error message is generated. However, the number of remaining table entries is not
decremented.
Delete point
The currently displayed point is deleted from the table. After deletion, the previous point is
displayed. If the table only consisted of one point before deletion, then the current measured
variable is displayed as a value pair.
Return
By selecting this point, you return to the function "
dip table mode
"
(033)
.
Next point
This scrolls down in the table. If the table is empty, you can still select this option.
However, the displayed value does not change.
Previous point
This scrolls up in the table. If the table is empty, you can still select this option.
However, the displayed value does not change.
"
Caution!
After entering one or more points into the dip table, make sure that the dip table is activated in the
"
table on
" dip table mode.