Micropilot S FMR533 4 to 20 mA HART
Commissioning
Hauser
57
Function "dip table" (034)
This function edits measured variable. The number behind the entry "
remain
" indicates the current
number of remaining free value pairs. The maximum number of value pairs is 32; after each entry,
the remaining number is decremented.
!
Note!
The
un
corrected measured value is displayed in the "
dip table
" (
034
) function.
This may differ considerably from the measured values when a dip table is activated.
Function "dip table" (035)
This function edits the dip value.
Function "dip table handl." (036)
Use this function to enter the dip value (level or distance) which will correct the measurement
values.
Selection:
•
new point
• edit point
• store point
• delete point
• return
• next point
• previous point
General procedure:
To enter a new point into the dip table, use
•
"new point"
to enter the value (pairs),
•
"store point"
to sort the new value (pairs)
•
"return"
to go to the dip table mode and
•
"table on"
to activate the dip table.
⇒