Micropilot S FMR533 4 to 20 mA HART
Commissioning
Hauser
53
Function "custody mode" (0A9)
This indicates the device calibration mode. The calibration mode (active) can be set using the
hardware security lock on the electronics (
Selection:
•
inactive
• active pos.
• active neg.
active pos.
The custody mode (device is lead-sealed and accurate to the nearest mm) is active and is held.
active neg.
Custody mode (device is lead-sealed and accurate to the nearest mm) is activated and not held, e.g.
because the signal-to-noise ratio is less than 5 dB (refer to function "
echo quality
"
(056)
in the
function group "
extended calibr.
"
(05)
).
"
Caution!
After entering all the values and completing mounting and aligning work, enter the Reset Code
"
555
" in the function "
reset
"
(0A3)
to reset the device history for auto-correction or set history
reset to "
yes
" in order to reset the device history for the auto-correction.
⇒
E HAUSER
E
+
–