5.2.13 Underground Refrigerant Piping
Refrigerant pipe installed underground should be routed inside a vapor-tight protective sleeve to prevent
deterioration of the insulation and water infiltration. Refrigerant pipe installed inside underground casing
must be continuous without any joints. Underground refrigerant pipe must be located at a level
below the
frost line
.
shows the arrangement of refrigerant pipe and cable(s) in a conduit.
conduit sizes for utility conduit.
Figure 5-11 Typical arrangement of pipe and cables in a utility conduit
Table 5-10 Utility-conduit sizes
Liquid Pipe
1
Vapor Pipe
1
3/8 (1-1/8
2,3
)
5/8 (2-1/8
2,4
)
3/8 (1-1/8)
3
4
4
1. OD pipe diameter in inches. Values in parentheses indicate OD of pipe with insulation
jacket.
2. Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required
thickness may vary based on surrounding ambient conditions and should be calculated
and specified by the design engineer.
3. Insulation thickness (value in parenthesis) = 3/8 inch.
4. Insulation thickness (value in parenthesis) = 1 inch.
Table 5-11 Heat-pump unit refrigerant-pipe connections (All brazed type)
Model
Liquid Conn., in. Vapor Conn., in.
SCR18, 24, 36
3/8
5/8
Vapor Line
Liquid Line
Min. 18 Gauge
Cable
Power/Communication
Pipe Sleeve
Insulation Material
Insulation
Material
Содержание Liebert SRC Series
Страница 1: ...Liebert SRC User Manual Mini Split Cooling System ...
Страница 2: ......
Страница 18: ...Safety Symbols Liebert SRC User Manual 8 Page intentionally left blank ...
Страница 20: ...Model Number and Nomenclature Liebert SRC User Manual 10 Page intentionally left blank ...
Страница 28: ...Product Introduction Liebert SRC User Manual 18 Page intentionally left blank ...
Страница 122: ...Troubleshooting Liebert SRC User Manual 112 Page intentionally left blank ...
Страница 123: ......