Piping
Liebert
®
SRC
™
User Manual
52
5.3.2.2 Bundling and Trap when Indoor Unit is above Outdoor Unit
1. Refer to
, and tape the piping, drain hose, and connection cable from down to up.
2. Secure the taped piping along the exterior wall using pipe clamps.
3. Create a trap above the electrical connections cover to prevent water from penetrating electrical
components and wiring.
Figure 5-17 Piping/Trap when indoor unit is above outdoor unit
5.3.2.3 Bundling and Trap when Indoor Unit is below Outdoor Unit
1. Refer to
, and tape and tape the piping, drain hose, and connection cable from down to up.
2. Secure the taped piping along the exterior wall using pipe clamps.
3. Create a trap above the electrical connections cover to prevent water from penetrating electrical
components and wiring.
Figure 5-18 Piping/Trap when indoor unit is below outdoor unit
Taping
Pipe Clamps
to Secure Pipe
Against Wal l
Drain hose
Pipings
Connecting cable
Seal small openings
around pipings with a
gum type sealant.
Trap is required to prevent water
from entering into electrical parts.
Seal a small opening
around the pipings
with gum type sealant .
Trap
Trap
Pipe Clamps
to Secure Pipe
Against Wall
Содержание Liebert SRC Series
Страница 1: ...Liebert SRC User Manual Mini Split Cooling System ...
Страница 2: ......
Страница 18: ...Safety Symbols Liebert SRC User Manual 8 Page intentionally left blank ...
Страница 20: ...Model Number and Nomenclature Liebert SRC User Manual 10 Page intentionally left blank ...
Страница 28: ...Product Introduction Liebert SRC User Manual 18 Page intentionally left blank ...
Страница 122: ...Troubleshooting Liebert SRC User Manual 112 Page intentionally left blank ...
Страница 123: ......