2.1 Electrical Data
10 Function Settings
Louver set-up.
1, 2, 3, 4, All = louver number.
STD = standard louver angle setting.
Angle of the louver.
Elevation grill set-up.
Grill up.
Grill closed.
Grill down.
Display lock set-up
Display is locked.
Display is not locked.
Set-up minimum-difference value between cooling and heating setpoints.
Set current time.
Set timer for schedule override.
Set-up default setback for cooling/heating temperature setpoints.
Clear the air-filter cleaning alarm.
Check the indoor-unit air filter and clean if necessary.
Table 2-1
Unit electrical data
Model
Nom. Tons
Compressor
Qty.
Compressor (A)
Cool/Heat
Fan
Qty.
ODU Fan (A) IDU Fan (A)
MCA (A)
MOP (A)
SRC18
1-1/2
1
14.6/14.6
1
0.25
0.40
19
25
SRC24
1-3/4
1
17.3/17.3
1
0.25
0.5
23
35
SRC36
2-3/4
1
17.3/17.3
1
0.25
0.5
23
35