Piping
Liebert
®
SRC
™
User Manual
46
A properly-installed pipe system has sufficient supports to prevent pipes from sagging during the life of the
system. As necessary, place supports closer for segments where potential sagging could occur. Maximum
spacing of the pipe supports must meet local codes.
If local codes do not specify pipe-support spacing, support the pipes as follows:
• Maximum of 5 feet on center for straight segments of pipe up to 3/4-in. outside diameter.
• Maximum of 6 feet on center for pipe up to 1-in. outside diameter.
• Maximum of 8 feet on center for pipe up to 2-in. outside diameter.
Wherever the pipe changes direction, place pipe clamps within 12 inches on one side and within 12 to 19
inches of bend on the other side, as shown in
Figure 5-9 Typical pipe-support location for a change in pipe direction
A
B
Pipe
Clamps
A + B 12”–19”