Piping
47
Liebert
®
SRC™ User Manual
5.2.12 Pipe Sleeves at Penetrations
Emerson requires that all pipe penetrations through walls, floors, and pipes buried underground be
properly-insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression
of refrigerant-pipe insulation and free movement of the pipe withing the sleeve,
Figure 5-10 Pipe sleeve options
NOTE
The diameter of the penetrations must be determined by the pipe diameter
plus the thickness of the insulation.