Installation
Liebert
®
SRC
™
User Manual
26
3.3.2
Indoor Unit Clearance
Follow recommended practices when choosing an indoor location for the wall-mounted indoor unit.
• Keep unit away from any indoor steam or excessive heat.
• No obstacles should be placed around the unit.
• Condensation drain (leakage piping) should be routed away from the unit.
• Do not install near a doorway.
• Clearance gap between any wall or enclosure and the left or right side of the unit must be greater than
4 inches,
• From the top of the unit to the ceiling, there must be greater 8 inches of clearance, see
.
• Unit should be at least 6.5 feet from the floor for adequate clearance.
Figure 3-8 Indoor unit clearance requirements
3.4 Installing the Indoor Unit
3.4.1
Mounting the Installation Plate to the Wall (SRC18)
Follow this procedure and best practices when mounting the indoor unit’s plate to a wall.
!
WARNING
Risk of electrical shock. Can cause injury or death.
• When choosing a location for the wall-mount plate, be sure to take into consideration routing of
wiring for power outlets within the wall. Avoid contact with hazardous voltage wiring.
• Use caution when drilling holes through the walls for the purposes of piping connections.
Refer to
3.4.3 - Drilling a Piping Hole in the Wall
, as you following the plate-installation
procedure.
!
WARNING
Risk of improper mounting.Can cause building and equipment damage, serious injury or death.
Consult a structural engineer to determine the suitability of the wall for mounting and the
recommended fastening method. Unit must be anchored tightly to a wall having sufficient strength
to support the unit during operation to prevent the unit from falling or creating excessive,
unnecessary vibration during operation.
Minimum clearance
from ceiling - 8”
More than 4 inches
More than
4 inches
At least 6.5 feet from the floor
Содержание Liebert SRC Series
Страница 1: ...Liebert SRC User Manual Mini Split Cooling System ...
Страница 2: ......
Страница 18: ...Safety Symbols Liebert SRC User Manual 8 Page intentionally left blank ...
Страница 20: ...Model Number and Nomenclature Liebert SRC User Manual 10 Page intentionally left blank ...
Страница 28: ...Product Introduction Liebert SRC User Manual 18 Page intentionally left blank ...
Страница 122: ...Troubleshooting Liebert SRC User Manual 112 Page intentionally left blank ...
Страница 123: ......