Operation
95
Liebert
®
SRC™ User Manual
3. Set the cooling setpoint by pressing
,
then adjust the temperature displayed
under Cool-temperature setpoint in the Temperature section of the display by pressing
.
4. Set the cooling setpoint by pressing
,
then adjust the temperature displayed
under Heat-temperature setpoint in the Temperature section of the display by pressing
.
8.5.7
Selecting Timed Override
Timed override temporarily overrides the current schedule (occupied/unoccupied).
• Reverts to last occupied schedule in unoccupied override.
• Reverts to last unoccupied schedule in occupied override.
See
, to set the duration of the override.
Press
for 3 seconds.
Timed override is enabled.
• To cancel timed override, press
for 3 seconds.
Operation reverts to last weekly schedule.
8.5.8
Selecting Set Back
Set Back reverts to the last unoccupied schedule until set-back operation is canceled. If there is no
unoccupied schedule, it returns to the default set-back setting. See
, to set the set-back setting.
Press .
Set back is enabled.
• To cancel set back, press
.
NOTE
• You cannot changes settings in set-back mode. HL and the lock is
displayed.
• Set back is canceled if a command from another controller is received.
COOL
HEAT
Содержание Liebert SRC Series
Страница 1: ...Liebert SRC User Manual Mini Split Cooling System ...
Страница 2: ......
Страница 18: ...Safety Symbols Liebert SRC User Manual 8 Page intentionally left blank ...
Страница 20: ...Model Number and Nomenclature Liebert SRC User Manual 10 Page intentionally left blank ...
Страница 28: ...Product Introduction Liebert SRC User Manual 18 Page intentionally left blank ...
Страница 122: ...Troubleshooting Liebert SRC User Manual 112 Page intentionally left blank ...
Страница 123: ......