Installation
29
Liebert
®
SRC™ User Manual
3.4.3
Drilling a Piping Hole in the Wall
Follow the left or right piping-clearance recommendations.
1. Using a 2-5/8 in. (0.65 mm) hole-core drill bits, drill a hole at either the right or left side of the wall
mounting,
• The slant of the hole should be 3/16 to 5/16 of an inch from level with an upward slant on the
indoor-unit side and downward on the outdoor-unit side.
2. Finish-off the newly-drilled hole as shown in
with a bushing and sleeve covering.
• The sleeve and bushing prevents damage to the tubing/bundling of the piping.
Figure 3-13 Drilling a piping hole
3.4.4
Mounting the Indoor Unit to the Plate
1. Hook the indoor unit onto the upper portion of the installation plate,
2. Engage the hooks at the top of the indoor unit with the upper edge of the installation plates.
• Make sure that the hooks are properly seated on the installation plate by moving the unit left and
right.
Figure 3-14 Hook the top of the unit to the plate
(3/16"~5/16")
Indoor
WALL
Outdoor
Bushing
Core Drill
Sleeve
Installation plate
Indoor uni t
3”
Spacer
1
2