Piping
37
Liebert
®
SRC™ User Manual
4. Carefully inspect the flared pipe end.
• Compare the geometry with
and the dimensions detailed in
and
Figure 5-2 Flared-connection dimensions
5.1.2
Tightening Flare Nuts
1. When connecting the flare nuts, coat the flare (inside and outside) with polyvinyl ether (PVE)
refrigeration oil only.
2. Initially, hand tighten the flare nuts using 3 or 4 turns.
3. Finishing tightening the flare nuts using both a torque wrench and a backup wrench as shown in
Figure 5-3 Tightening the flare nuts
Table 5-1
Flared-connection dimensions
Pipe
“A”
Thickness
Vapor (in. O.D.)
Liquid (in. O.D.)
Vapor (in.)
Liquid (in.)
Vapor (in.)
Liquid (in.)
1/2
1/4
1/8
1/16
1/8
1/8
5/8
3/8
1/8
1/16
1/16
1/8
NOTE
Do not use polyolyester (POE) or any other type of mineral oil as a thread
lubricant. These lubricants are not compatible with PVE oil used in this system
and create oil sludge leading to equipment damage and system malfunction.
Table 5-2
Tightening torque for flare nuts
Pipe size (in. O.D.)
Tightening torque (ft-lbs)
Width of flare (A [in.])
1/4
∅
13.9 – 18
1/8
3/8
∅
24.5 – 30.3
1/8
1/2
∅
39.7 – 47.7
1/8
5/8
∅
45.5 – 59.2
1/16
90°
2
45°
2
A
R=0.4~0.8
Union
Содержание Liebert SRC Series
Страница 1: ...Liebert SRC User Manual Mini Split Cooling System ...
Страница 2: ......
Страница 18: ...Safety Symbols Liebert SRC User Manual 8 Page intentionally left blank ...
Страница 20: ...Model Number and Nomenclature Liebert SRC User Manual 10 Page intentionally left blank ...
Страница 28: ...Product Introduction Liebert SRC User Manual 18 Page intentionally left blank ...
Страница 122: ...Troubleshooting Liebert SRC User Manual 112 Page intentionally left blank ...
Страница 123: ......