Troubleshooting
Liebert
®
CRV
™
174
Water drops carried
by airflow
Room humidity is over acceptable limit
Check room condition
Condensate pan drain is clogged
Contact your local Emerson representative
Problem with humidifier control
Contact your local Emerson representative
Water on the floor
around the unit
Unit is not properly leveled
Adjust the leveling feet
Unit condensate drain pipe is clogged
Remove pipe obstruction
Chilled water and water/glycol units: leak
in the water circuit
Locate and repair the leak
Piping insulation broken/damaged
Restore insulation integrity
Leak in the draining circuit
Contact your local Emerson representative
Condensate pump is faulty
Contact your local Emerson representative
Leak in the humidifier filling hose
Contact your local Emerson representative
Unsteady air
delivery
temperature
Incorrect positioning of remote
temperature sensor(s)
Verify correct positioning of temperature sensors
Unbalanced heat load distribution
Redistribute rack heat load
Remote temperature sensor(s) issue
Contact your local Emerson representative
Faulty temperature sensor(s)
Contact your local Emerson representative
Unit controller issue
Contact your local Emerson representative
Local display is not
operational but unit
operates
Local display cable disconnected
Connect cable
Local display cable damaged
Replace cable
Local display configuration lost
Contact your local Emerson representative
Local display is not
operational and unit
does not operate
Unit electrical supply is Off
Restore electrical supply
Unit main switch is Off
Switch On the unit
Control board supply issue
Contact your local Emerson representative
Control board issue
Contact your local Emerson representative
Table 41
Liebert iCOM
®
medium control board DIPswitch settings
DIPswitch
Number
Compressorized
CRV Models
CR019, CR020
and CR035
Chilled Water
Model-CR040
1
On
Off
2
Off
Off
3
On
Off
4
Off
Off
5
Off
Off
6
Off
Off
7
Off
On
8
On
On
Table 40
Unit diagnostics
Problem
Possible Cause
Corrective Action