Liebert iCOM
®
Control
127
Liebert
®
CRV
™
Figure 113 Service menus
—
Options setup parameters - Page 2
S413 WA and AL Relay
—Defines if the relays are normally On (and fall to Off in case of an event) or
normally Off (and change to On in case of an event).
S419 Dehumidification Enabled
—Selects whether the compressor or valve will be used to
dehumidify when the humidity is above the setpoint.
S420 Auto Restart Enabled
—This parameter, when set to
YES,
restarts the unit after a power
cycle. When this parameter is set to
NO,
then the unit will not restart (Turn On) after a power cycle.
S421 Single Unit Auto Restart
—Sets a time delay for the unit to restart when the Auto Restart
Enabled is set to
YES
. The delay, adjustable from 0-999 seconds, begins once the boot process has
completed. This parameter allows units to be staggered On to reduce the amount of simultaneous
power consumption after a loss of power.
S422 On-Off Enabled
—Disables the power button on the front of the display. Prevents the user
from turning Off the equipment from the User or System view. When this parameter is set to Off and
the user attempts to turn Off the unit, a message will appear stating “On-Off is disabled!” The default
configuration is On.
Figure 114 Service menus
—
Options setup parameters - Page 3
S424 Chilled Water Quick Start
—Can be enabled only for chilled water units. This function allows
to restart a Liebert CRV after a power cycle within approximately 10 seconds.
During quick start, the control is not active. The digital output for the fan activates, the fan speed
operates on the voltage selected on S426 and the chilled water valve opens to the voltage set in S427.
When quick start is enabled:
• S425 Fan Digital Output P2-3 changes to
On
(cannot be changed by the user)
• S426 Fan Analog Output P14-1 changes to
7.5V
(can be changed by the user)
• S427 Valve Analog Output P14-3 changes to
7.5V
(can be changed by the user)
After each power cycle, the Liebert CRV will adjust fan and cooling output according to the
settings on lines S426 and S427. These user-defined settings will override the actual call for fan
and cooing until the delay set on S428 has elapsed.
Setup Parameters Chilled Water Unit
Options Setup Parameters DX unit