Electrical Connections
Liebert
®
CRV
™
60
Figure 36 CANbus communication connection Liebert CRV and Liebert MC (premium) unit
1
INPU
T
2
3
CA
N H
TB50
OUT
PUT
1
2
3
TB49
CA
N L
A
70
71
230
SH
1
INPUT
2
3
CAN H
TB50
TB49
OUTPUT
1
2
3
CAN L
H
L
H
L
BA
3
1
D58
P80
J6
TB
50
J4
TB
49
P15
BO
OT
SY
S
APP
PS
WD
3
1
CAN
ON
SW6
CAN
ON
SW6
3
1
J6
B
1
3
1
P78
A
B
DPN002841
Rev. 0
CAN Cable (A)
Connection
Shield
Connection
Shield Connection
Remove Jumper
Heat Rejection
Interlock (B)
Detail1
CAN Cable (A) Connection
Low-Voltage Field
Entrance Located
on Bottom Left of
Condenser Enclosure
Factory Wiring
Between Liebert
MC Control Board
and Terminal Strip
Condenser
Heat Rejection
Interlock (B)
Factory Wiring Between Liebert iCOM
and Terminal Strip
Liebert CRV Indoor Unit
COMPONENT NOTES
1. Component appearance, orientation and position may vary.
Terminal names and callouts remain constant.
CABLE NOTES (A)
:
1. Field Supplied Cable.
● Shielded
● 22-18awg Stranded Tinned Copper
● Twisted Pair (minimum 8 twists per foot)
● Low capacitance (15pf/ft or less)
● Must be rated to meet local codes and conditions.
● Examples Belden 89207 (plenum rated), or alpha wire 6454 Category 5, 5e or higher.
2. Do not run in same conduit, raceway or chase as high-voltage wiring.
3. For CANbus network lengths greater than 350ft (107m), contact Liebert factory.
WIRE NOTES (B)
1. Field Supplied Wire
● 18AWG or greater
● Rated 600V
2. Run two wires from indoor unit to condenser(s).