Electrical Connections
Liebert
®
CRV
™
70
Figure 45 Liebert IntelliSlot cable routing—Bottom entry, 300mm (12") DX models
Secure tie the field wiring shielded cable to
the rail. Route the shielded cable up toward
the Liebert IntelliSlots and fasten to the side rails
as needed.
DPN002814
Pg. 2, Rev. 3
Low-voltage field wiring
(shielded cable)
Low-voltage field wiring
(twisted pair)
SOME COMPONENTS NOT SHOWN FOR CLARITY
General wire routing paths shown. Wiring must be
run in conduit and must be inside Liebert CRV frame
and panels. Attach conduit to inside of rails with
cable ties.
Shielded cable may be used. If not, control wiring
must be run in separate conduit from power wiring.
Secure the control wiring or conduit to the bottom
edge of the rail with cable ties. Route the shielded
cable up toward the Liebert IntelliSlot bays and
fasten to the side rails as needed.