Refrigerant Connections for Air-Cooled Units
Liebert
®
CRV
™
34
6.3
Liebert MC Condenser Selection—600mm (24") and 300mm (12")CRV Units
6.4
Liebert Fin/Tube Condenser Selection—600mm (24") Units
6.5
General Piping Layout
1. Piping must be Type ACR copper tubing and sized per
and
.
Use the shortest possible refrigeration pipelines to minimize the total charge of refrigerant and
the number of pressure drops.
2. Minimize the number of bends and make the bends the largest radius practical to prevent
constricting refrigerant flow.
3. Insulate the piping as specified in
. If the pipes are installed next to electrical cables, they
must be isolated from the building using vibration-isolating supports to avoid damage to cable
insulation.
4. There must be at least one inch (25mm) separation between the gas and liquid pipelines. If this is
not possible, insulate both lines.
5. Support both horizontal and vertical pipes with vibration-damping clamps, which include rubber
gaskets. Place these clamps every 5 to 7 ft. (1.5 to 2m).
Table 6
Traditional open room 95°F (35°C)/23RH return air conditions
Indoor
Model
Unit
Width
Outdoor Design Ambient Temperature, °F (°C)
95 (35)
100 (38)
105 (41)
110 (43)
115 (46)
120 (49)
CR019R*
300mm
(12")
MCS028E1
MCM040E1
MCM040E1
MCM040E1
MCL055E1
MCL055E1
CR020A
600mm
(24")
CR035A
MCM040E1
MCL055E1
MCL055E1
MCM080E1
MCM080E1
MCM080E1
* 300mm (12") DX model
Table 7
Traditional open room 95°F (35°C)/23RH return air conditions Liebert QuietLine
™
sound
levels
Indoor
Model
Unit
Width
Outdoor Design Ambient Temperature, °F (°C)
95 (35)
100 (38)
105 (41)
110 (43)
115 (46)
120 (49)
CR019R*
300mm
(12")
MCS028E1
MCM040E1
MCL055E1
MCL055E1
MCM080E1
—
CR020A
600mm
(24")
—
CR035A
MCL055E1
MCL055E1
MCM080E1
MCM080E1
MCL110E1
—
* 300mm (12") DX model
Table 8
Traditional open room 95°F (35°C)/23RH return air conditions
Model No.
Unit
Width
Ambient Temperature Selection
95°F (35°C)
100°F (38°C)
VFD Units
Units with
Liebert Lee-Temp
VFD Units
Units with
Liebert Lee-Temp
CR020A
600mm
(24")
TCSV28K
TCSV60K
DCSL28K
DCSL60K
TCSV60K
TCSV90K
DCSL60K
DCSL90K
CR035A
NOTE
All field-installed piping must comply with applicable national, state and local codes.