Liebert iCOM
®
Control
121
Liebert
®
CRV
™
S605 Calibrated Return Humidity
—Shows the adjusted humidity value of the return sensor. This
value is the actual sensor reading (+ or -) the offset “Return Humidity.”
S606 Digiscroll 1 NTC
—Adjusts the digital scroll 1 NTC reading from the actual sensor to
compensate for any error or drift of the sensor.
S607 Calibrated Digiscroll 1 NTC
—Shows the adjusted Digital Scroll 1 NTC sensor value. This
value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC.”
Figure 105 Service menus
—
Sensor calibration / setup parameters
—
Page 2
S613 T Sensor PTC or NTC
—Selects the type of sensor being used for the return air sensor.
S614 Return T Sensor
—Provides an offset to the actual sensor reading to calibrate the unit’s sensor
to other sensors.
S615 Calibrated Return T Sensor
—Shows the reading after the offset has been added to or
subtracted from the actual sensor reading.
S616 Supply T Sensor PTC or NTC
—Sets the type of sensor that is connected to the unit. It is set
at the factory as NTC and should be changed only by a certified Emerson technician.
S617 Supply T Sensor
—Provides an offset to the actual sensor reading to calibrate the unit’s sensor
to other sensors.
S618 Calibrated Supply T Sensor
—Shows the reading after the offset has been added to or
subtracted from the actual sensor reading.
S619 CW T Sensor
—Provides an offset to the actual sensor reading to calibrate the unit's sensor to
other sensors.
S620 Calibrated CW T Sensor
—Shows the reading after the offset has been added to or subtracted
from the actual sensor reading.
Figure 106 Service menus
—
Sensor calibration / setup parameters - Page 3
This unit can be equipped with a total of 20 rack sensor readings or ten 2T temperature sensor
modules. This menu permits temperature sensor calibration by entering a negative or positive offset.
The calibrated reading is displayed in the far right column. If a value is not shown in the far right
column, then the sensor is either not set up correctly or is not connected.
Sensor Calibration for CW Models
Sensor Calibration for DX Models