Liebert iCOM
®
Control
Liebert
®
CRV
™
114
11.8 Service
—
Diagnostics Menu Screens
Figure 91 Service menus
—
Diagnostics / service mode parameters screen - Page 1
S302 HP 1 Alarm Code
—Compressor 1 high pressure alarm code.
S303 LP 1 Alarm Code
—Indicates which phase Compressor 1 is operating in. For more information,
refer to the Liebert iCOM Training and Service manual’s low pressure transducer flow chart.
S304 HT 1 Alarm Counter
—Compressor 1 high temperature event alarm counter. If more than five
events in a rolling 4 hour period occur, then the compressor will be locked out.
S305 12h Dehum Counter
—Is a counter that counts A136 Dehum Timer times out.
• If the Dehum Timer is used 3 times in any rolling 12 hour period Dehum needs to be disabled for
12 hours.
• A message is generated “Dehum Suspended 12hrs”).
The message can be disabled in the Service - Set Alarms menu.
• The counter resets to 0 on a power cycle and can be manually reset via Display.
• When Dehum is enabled again, a message is be generated “Dehum Resumed.” The message can
be disabled in the Service - Set Alarms menu.
S306 Low Supply Temperature Counter
—It increases by 1 each time the low supply temperature
event is triggered.
S307Actual LP1 Pressure
—Current refrigerant low pressure side reading in atmosphere for
Compressor 1.
S308 Actual HP1 Pressure
—Current refrigerant high pressure side liquid reading in atmospheres
for Compressor 1. (This is available only on water-cooled units equipped with a motorized ball valve.)
Figure 92 Service menus
—
Diagnostics / service mode parameters screen - Page 2
Lines S302-S304, S308 and
S310 are not displayed on
chilled water models.
Lines S315-S318 are
not displayed on
chilled water models.