Remote Rack Sensor Wiring
141
Liebert
®
CRV
™
13.2 Set 2T Rack Sensor Identities-DIP Switch settings
1. Confirm the DIP switches are set correctly for 2T sensors numbered 1, 2 and 3.
2. If additional sensors are to be connected to a cooling unit:
a. Apply numbered stickers to the sensor housings, corresponding to sensor chain position.
b. Based on the sensor number, use the included DIP switch tool to set the DIP switches
according to the table above. If you are having difficulty setting switches through the opening
in the housing or if the hole is not present, you may open the case by removing the three
Phillips head screws. Reassemble housing once complete.
Figure 124 Setting DIP switches for 2T sensors
Table 36
DIP switch settings
2T Temperature and
Humidity Sensor
DIP Switch Position
Factory-Set
to Terminated
1
2
3
4
5
6
7
8
Included with Liebert CRV
Sensor # 1
Off
Off
On
Off
On
Off
Off
Off
-
Sensor # 2
On
Off
On
Off
-
Sensor # 3
Off
On
On
Off
Yes
Optional 2T Rack Sensors
Sensor # 4
On
On
On
Off
On
Off
Off
Off
-
Sensor # 5
Off
Off
Off
On
-
Sensor # 6
On
Off
Off
On
-
Sensor # 7
Off
On
Off
On
-
Sensor # 8
On
On
Off
On
-
Sensor # 9
Off
Off
On
On
-
Sensor # 10
On
Off
On
On
-
NOTE
Use a field-supplied DIP switch tool (or similar non-conductive tool) to move the DIP switches.
Do not insert any metal object into the sensor case.
Non-Conductive
DIP Switch Tool
(field-supplied)
2T Sensor Terminal
Housing DIP switch hole
2T Sensor Housing Case Opened