Maintenance
163
Liebert
®
CRV
™
Table 39
Maintenance schedule
Component
Maintenance Period
Monthly
By User
Every
3 Months
Every
6 Months
Annually
General
Check unit display for clogged-filter warning
X
Check for irregular noise from unit fans
X
Check for irregular noise from compressor (if
applicable)
X
Check for irregular noise from remote
condenser fan(s) (if applicable)
X
Filters
Check state of filters
X
Replace air filter if necessary
X
Check filter switch functionality
X
Blowers
Verify impellers move freely
X
Check bearings
X
Check motor mounts for tightness
X
Check fan safety switch
X
Electrical/Electronics
Check condition of contacts
X
Check electrical connections
X
Check operation of controller
X
Check unit operation sequence
X
Steam-Generating
Humidifier
Check cylinder and pan
X
Check condition of steam hoses
X
Verify filling solenoid valve is operating properly
X
Cooling Water Circuit
(Water/Glycol and
Chilled Water Units)
Check circuit for leakage/general condition
X
Check water (glycol) inlet temperature
X
Check water regulating valve operation
X
Check in/out water (glycol)
Δ
t
X
Check mixture glycol level (if applicable)
X
Refrigerating Circuit
Check compressor noise/vibrations
X
Check oil level through compressor sight glass
X
Adjust/tighten compressor/functional elements
X
Check sight glass for problem detection
X
Check starting/running amps
X
Check refrigerating circuit main pressures
X
Check compressor suction superheat
X
Check discharge temperature
X
Check subcooling
X
Air-Cooled
Condenser/Drycooler
(if applicable)
Check fan bearings
X
Check fan motor mounts for tightness
X
Check coil condition
X
Check pipeline supports
X
Check fan speed controller operation
X
Water/Glycol Pump
See manual for the pump