Liebert iCOM
®
Control
Liebert
®
CRV
™
120
Figure 102 Service menus
—
Set alarms parameters screen - Page 4
This screen determines the operation of an active alarm. Each event can be enabled or disabled and
can be set to operate as an alarm, warning or message. The delay is the time the control waits before
reporting the event.
Figure 103 Service menus
—
Set alarms parameters screen - Page 6
11.10 Service
—
Sensor Calibration Menu Screens
Figure 104 Service menusFigure 89 Sensor calibration / setup parameters - Page 1
S602 Return Temperature
—Adjusts the return temperature reading from the actual sensor to
compensate for any error of the sensor or to match other sensors in the room.
S630 Calibrated Return Temperature
—Shows the adjusted temperature value of the return
sensor. This value is the actual sensor reading (+ or -) the offset “Return Temperature.”
S604 Return Humidity
—This parameter adjusts the return humidity reading from the actual
sensor to compensate for any error of the sensor or to match other sensors in the room.
Set Alarms Parameters for DX
Set Alarms Parameters for CW