Liebert iCOM
®
Control
Liebert
®
CRV
™
122
Figure 107 Service menus
—
Sensor calibration / setup parameters - Page 4
This unit can be equipped with a total of 20 rack sensor readings or ten 2T temperature sensor
modules. This menu permits temperature sensor calibration by entering a negative or positive offset.
The calibrated reading is displayed in the far right column. If a value is not shown in the far right
column, then the sensor is either not setup correctly or is not connected.
11.11 Service
—
System/Network Unit-Level Setup Menu Screens
Figure 108 Service menus
—
System / network setup parameters-System - Page 1 for the Display
S802 Number of Connected Units
—Sets the number of units that will be viewable from the large
display [1 - 32] and will participate on the unit to unit network.
S803 Teamwork Mode
—Selects which teamwork mode to use within a selected group. Teamwork
modes are:
0 = 0 No
1 = 1 Parallel
2 = 2 Independent
3 = 3 Optimized Aisle
S804 Teamwork Mode is Based on
—Two selections are available: Average and Maximum.
Average
: Allows the temperature/humidity control to be based on an average reading of the
controlling sensors.
Maximum
: Allows the temperature/humidity control to be based on the highest controlling
sensor reading.
S805 Qty Units Included in Average
—Allows choosing an average of the highest sensor readings
for the calculation.
S808 Lock for Upgrade
—Locks the Liebert iCOM functions to permit upgrading its firmware.