Liebert iCOM
®
Control
Liebert
®
CRV
™
112
Figure 87 Service menus
—
Wellness motor settings parameters screen - Page 2
S013 Number of Starts
—Shows the number of starts for the unit’s fans.
S014 Run Hours
—Shows the number of run hours for the unit’s fan.
S015 Average Run Time
—Displays the average run time of the unit’s fan.
S016 Starts per Day Best
—Displays the lowest number of starts in a rolling 24 hour period.
S017 Starts per Day Worst
—Displays the highest number of starts in a rolling 24 hour period.
S018 Number of Alarms
—Displays the number of alarms that have occurred with the unit’s fans.
S019 Actual Bonus
—Displays the actual calculation of wellness for the unit’s fans. The unit will
always take the value from the worst component for the next maintenance indication.
Figure 88 Service menus
—
Wellness compressor 1 settings parameters screen - Page 3
S024 Number of Starts
—Shows the number of starts for the unit’s compressor.
S025 Run Hours
—Shows the number of run hours for the unit’s compressor.
S026 Average Run Time
—Displays the average run time of the unit’s compressor.
S027 Starts per Day Best
—Displays the lowest number of starts in a rolling 24 hour period.
S028 Starts per Day Worst
—Displays the highest number of starts in a rolling 24 hour period.
S029 Number of HP Alarms
—Displays the number of high pressure alarms that have occurred
with the unit’s compressor.
S030 Number of LP Alarms
—Displays the number of low pressure alarms that have occurred with
the unit's compressor.
S031 Number of OL Alarms
—Displays the number of overload alarms that have occurred with the
unit's compressor.
S032 Number of DS HT Alarms
—Displays the number of Digital Scroll High Temperature alarms
that have occurred with the unit's compressor.
S033 Actual Bonus
—Displays the actual calculation of wellness for the unit’s compressor. The unit
will always take the value from the worst component for the next maintenance indication.