Electrical Connections
Liebert
®
CRV
™
58
9.1.2 Electrical Connections for Optional Features—600mm (24") models
(Source: DPN001884, Rev. 5, Page 2)
13.
Condensate Pump High Water Alarm (available when optional pump is installed)
—On
pump high water indication, normally open dry contact is closed across Terminals 88 and 89 for
remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
14.
Liebert Liqui-tect
®
Shutdown and Dry Contact (Available When Optional Liebert
Liqui-tect Sensor is Installed)
—On Liebert Liqui-tect activation, normally open dry contact is
closed across Terminals 58 and 59 for remote indication. The Liebert Liqui-tect sensor notifies
Liebert iCOM
®
of indication through Terminals 60 and 61. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
15.
Reheat and humidifier lockout
—Remote 24VAC required at Terminals 82 and 83 for lockout
of reheat and humidifier.
16.
Additional Common Alarm
—On any alarm, one additional normally open dry contact is closed
across Terminals 94 and 95 for remote indication. 1A, 24VAC maximum load. Use field-supplied
Class 1 wiring.
NOTICE
Risk of improper input power. Can cause equipment damage.
The electronically commutated motors included in the Liebert CRV unit —included in 480V
CR035 and CR040 units—are suitable for connection to an electrical service providing input
power to the unit with 300V or less line-to-ground potential only.
Acceptable unit input electrical service for 460V (480V) nominal units:
• 480V wye with solidly grounded neutral and 277V line-to-ground
Unacceptable unit input electrical service for 460V (480V) nominal units:
• Wye with high resistance (or impedance) ground
• Delta without ground or with floating ground
• Delta with corner ground
• Delta with grounded center tap
NOTE
Refer to specification sheet for total unit full load amps, wire size amps and maximum
overcurrent protective device size.