9 System Options
iConnect
Installation Manual
53
9.17.
Standard Type
By choosing one of the existing security standards you can change the Control System behavior accordingly.
To set the standard type:
1.
From the Programming menu, select System Options, Standard Type [9417].
2.
Select Regular, EN-50131 or Skafor.
9.17.1.
EN-50131 Standard Type
Settings the Standard type to EN-50131 changes some of the Control System settings as described below.
Arm Prevention for EN-50131
The system cannot be armed in the following cases:
•
Media Loss, Supervision Loss, or Device Trouble condition in all Active Communication1 modules --
GPRS and/or GSM, and/or PSTN2;
•
Trouble condition (Transmitter Out of Synch, Supervision Loss, or Zone Trouble) from any Zone,
including Fire, Gas, Flood, and Environmental;
•
Entry/Exit Trouble - System not ready is displayed on the Control System’s LCD.
In an attempt to remotely arm the system the remote arming device is notified as follows:
•
When arming by SMS – an SMS message "Command refused" is sent to the cellular phone;
•
When arming by DTMF – a negative error tone is sounded;
•
When arming from WUApp – System not Ready message is displayed.
Tamper Behavior for EN-50131
Opening of any tamper switch while the Control System is disarmed causes the Control System to send an alert. If the
EN-50131 standard is chosen, the siren is not activated in this case. For other standards (Skafor, Regular), the siren is
activated.
Number of Events from Single Source for EN-50131
The EN-50131 standard requires that the system avoid multiple events being generated from a single source. The
number of repeated events from the same source during any Arm or Disarm period is limited to three. Two kinds of
event types are defined for each device: Alarm/Tamper event and fault/trouble event. Every device can have maximum
of three events from each type registered in the log. After the third event from the same source, no more events are sent
to CS. Counters are reset each time the system is armed or disarmed.
EN-50131 Required Settings
To meet the requirements of the EN-50131 standard:
•
Set Supervision Time to 2 hours – see p.36,
7.2.3 Supervision Time;
•
Set Supervised Arm to 20 minutes – see p. 47,
9.3.3 Supervised Arm;
•
Set Entry Delay to 45 sec. maximum – see p. 43,
8.1 Entry/Exit Delay;
•
Set Arm Status Display to 30 sec. -- see p. 48,
9.6.1 Arm Status Display;
•
Set Entry/Exit Trouble to "Enabled"
1
Active communication module is a module used for events reporting.
2
If there is only one communication module (GPRS, PSTN, or GSM), any communication trouble prevents the Control System from
arming.
Содержание iconnect
Страница 79: ...Appendix A Menu Structure iConnect Installation Manual 75 ...
Страница 80: ...Appendix A Menu Structure iConnect Installation Manual 76 ...
Страница 81: ...Appendix A Menu Structure iConnect Installation Manual 77 ...
Страница 82: ...Appendix A Menu Structure iConnect Installation Manual 78 ...
Страница 83: ...Appendix A Menu Structure iConnect Installation Manual 79 ...
Страница 84: ...Appendix A Menu Structure iConnect Installation Manual 80 ...