BO08A01KNXFI01010002.DOC
Din Rail 8 Output Module– Product Handbook
8/51
Eelectron SpA, Via Magenta 77/22, I-20017 Rho (MI), Italia
+39 02.9316681 +39 02.93507688
[email protected] www.eelectron.com
BO08A01KNXFI01010002.DOC
C.F. e P.IVA 11666760159
Capitale sociale: 800.000,00€ interamente versato
Tribunale di Milano 359157-8760-07
CCIAA Milano 148549
4. Output Configuration
KNX PARAMETER
SETTINGS
FAN COIL ACTUATOR (Output 1,2,3,4,5)
Disable
Enable
This parameter defines whether the outputs from 1 to 5 are configured to manage fan coils, if the
function is enabled outputs 6, 7 and 8 remain available as output for generic loads or electric
valves control; outputs 7 and 8 can be still configured for control of shutters / blinds or motor
reduction driver.
Output 1 – 2 Configuration
Output are independent
Output are coupled
Here it is possible to set if outputs are independent and therefore can be set with functions which
use only one relay at a time (generic loads and electric valve); if the option selected is “Output are
coupled” the relays work together to realize functions which use a double relay (shutter and motor
reduction driver)
Output 3 – 4 Configuration
Same values of “Output 1 – 2 Configuration”
Output 5 – 6 Configuration
Same values of “Output 1 – 2 Configuration”
Output 7 – 8 Configuration
Same values of “Output 1 – 2 Configuration”