6.7. Function ON with delay / timing OFF
After receiving a telegram from the Relay Command Object, the relay is active for a time (T
LS
) that
can be set by a parameter; when T
LS
expires, it turns off automatically.
It is also possible to set a delay on activation time (T
ON
) (see “ON with delay” function).
KNX PARAMETER
SETTINGS
Delay on Activation
True
False
Delay on Activation (Base Time)
1 sec.
1 minute
1 hour
Delay on Activation (Factor)
1…255
The delay time between the receipt of a telegram and the execution of the command is given by :
Delay of Activation Time = Delay on Activation (Base Time) x Delay on Activation (Factor)
Timing (Base Time)
1 sec.
1 minute
1 hour
Timing (Factor)
1…255
The T
LS
time set for automatic turn off is given by :
Timing duration = Timing (Base Time) x Timing (Factor)