6.3. Relay Functions
KNX PARAMETER
SETTINGS
Function
ON / OFF
ON / OFF with delay
ON with delay / timing OFF
Continuous Switching
ON / OFF
After receiving a telegram on the switching objects, relay switch
in ON or OFF position.
ON / OFF with delay
it is possible to set a delay between the reception of a telegram
and the switch of the relay ; for both telegrams: activation and
deactivation
ON with delay / timing OFF it is possible to set a delay between the reception of a telegram
of activation and the switch of the relay; the OFF switch is
automatic after a configurable time (staircase timer)
Continuous switching
with this function the relay, when a 1 bit telegram is received,
starts switching ON and OFF with a configurable time; with the
opposite 1 bit telegram it stops and remains in OFF position.
Activation telegram
Telegram “0”
Telegram “1”
For every function above selected you can set a parameter to determine if the function is activated
with a telegram "0" (and then off with "1") or is activated with telegram "1" (and then off with "0");