6.10. Logic Function
Enabling logical operation allow to submit the command for the output to a result of a logical
operation between the communication object <
Output x> Relay Control
and another
communication object called
<Output x> Logic Function
.
By ETS is possible to select the logical operation to use, every time a telegram is received on the
logical object or on the control object the logical operation is calculated again and the result is
taken as a command for the relay.
KNX PARAMETER
SETTINGS
Logic function
AND
OR
XOR
This parameter selects the logical operation
Initial Value for logic Operation
Value “0”
Value “1”
This parameter selects the value the logical object must have on power up (
see note 1
).
If the relay has a timing, or a delay on activation or deactivation, etc… a logical operation result
that bring to command “0” or “1” determines a new behaviour of the relay that follows its own
parameterization.
NOTES:
[1]
: The value assumed by the logic communication object set by the parameter “Initial Value for
logic Operation” does not switch automatically the relay because this behaviuor is determined by
the parameter “Behaviour on power up”