7.3. Lock
Function
When lock function is enabled it allows, as a result of receiving a telegram on the
<Output x> Lock
Function;
to switch the relay in a defined state and force it to maintain this state even if the object
switching value changes. The behaviour of the lock function is the same described in par.
6.11
Lock
Function
.
This function can be enabled or with 1 bit commands than with 1 byte commands.
KNX PARAMETER
SETTINGS
Initial Value for Lock Object
Value “0”
Value “1”
This parameter selects the value of the lock object after a power on; appropriately changing this
value it is possible to start the output channel related to the lock function as “locked” or
“unlocked”. (
See note 1
).
Telegram for Lock Activation
Telegram “0”
Telegram “1”
This parameter selects the values associated to the “lock” or “unlock” condition.
Valve Position when Lock is Active
Valve Open
Valve Close
This parameter selects the state the valve must assume when the “lock function” becomes active”.
(
See note 2
).
Position when Lock Ends
Valve Open
Valve Close
Keep previous state and ignore telegrams
Keep previous state and don’t ignore
telegrams