3. General Parameter Configuration
3.1. Parameters
General Parameter Configuration Page list generic parameters which affects all output channels,
or their selection applies to all contacts of the input device simultaneously regardless of the
function selected later for each.
KNX PARAMETER
SETTINGS
Delay on Power-up (3-15 sec)
2 ÷ 15 seconds
Through this parameter is possible to set the delay of transmission of telegrams after a power on
by selecting the time by which the device is allowed to send telegrams.
In large systems after a power failure or shutdown this delay avoids to generate excessive traffic
on the bus, causing slow performance or a transmission block.
If there are different devices that require sending telegrams on the bus after a reset, these delays
must be programmed to prevent traffic congestion during the initialization phase.
The input detection and the values of objects are updated accordingly at the end of the
transmission delay time
At the end of ETS programming the device behaves like after a power on.