8.6. Lock
Function
When lock function is enabled it allows, as a result of receiving a telegram on the
<Channel x>
Lock Function;
to set the shutter in a defined position and force it to maintain this position even if
the channel receives move commands.
KNX PARAMETER
SETTINGS
Initial Value for Lock Object
Value “0”
Value “1”
This parameter selects the value of the lock object after a power on; appropriately changing this
value it is possible to have the shutter channel related to the lock function as “locked” or
“unlocked”. (
See note 1
).
Lock Activation Telegram
Telegram “0”
Telegram “1”
This parameter selects the values associated to the “lock” or “unlock” condition.
Shutter Position when Lock is Active
Move Up
Move Down
Stop – no movement
This parameter selects the state the relay must assume when the “lock function” becomes active”.
(
See note 2
).
NOTES:
[1]
: If the parameter “Initial Value for Lock Object” has the same value of “Telegram for Lock
Activation” happens that, on power up, the shutter channel starts in lock mode, waiting for a
“unlock” telegram in order to become active. Note that, even if the shutter channel starts with lock
function active it does not go automatically in the position defined by the parameter “Shutter
Position when Lock is Active “avoiding to have automatic and unexpected movements when the
power returns after a black out.